The A100 is a compact, high output, 110dB(A) alarm sounder. CPR complaint, EN54-3 tested and UL/cUL and ULC approved. Featuring 64 alarm tone frequencies and 4 remotely activated stages/channels.
| category | |
|---|---|
| Solutions |
| Maximum output: | 110dB(A) @ 1 m ±3dB[101dB(A) @ 10ft/3m ±3dB] |
| Nominal output: | 102dB(A) @ 1m ±3dB[93dB(A) @ 10ft/3m ±3dB] |
| No. of tones: | 64 (UKOOA / PFEER compliant) |
| No. of stages: | 4 |
| Volume control: | -12dB(A) tone dependent |
| Effective range: | 38m/124ft @ 1KHz |
| Voltages DC: | 10-60V dc |
| Voltages AC: | 24-260V ac 50/60Hz / 60-260Vdc |
| In rush: | 636mA within 4.0ms @ 24Vdc |
| Stage switching: | Negative (common positive) |
| Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
| Ingress protection: | IP66 Type 3R/13 |
| Enclosure: | High impact UL94 V0 & 5VA FR ABS |
| Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
| Line monitoring: | Diode polarized for use in supervised circuits |
| Operating: | -40 to +66°C [-40° to +151°F] |
| Storage: | -40 to +70°C [-40° to +158°F] |
| Relative humidity: | 95% at 20°C [68°F] |
| Vibration test: | 35Hz for a duration 4Hr (UL464) |
| Jarring test: | 3ft/lb Energy (UL464) |
| Impact test: | 3x 5lb (UL464) |
| MTBF DC: | 225.16 years / 1,972,386 hours – MIL 217 |
| MTBF AC: | 138.96 years / 1,217,285 hours – MIL 217 |
| Weight DC: | 0.26kg / 0.57lbs |
| Weight AC: | 0.37kg / 0.81lbs |